WILLIAMS FIELD SERVICES

hazardous_liquid Incident — — July 13, 2016

Incident Information

Incident DateJuly 13, 2016
OperatorWILLIAMS FIELD SERVICES
CommodityHVL OR OTHER FLAMMABLE OR TOXIC FLUID WHICH IS A GAS AT AMBI
Pipeline Typehazardous_liquid

Location

State
Coordinates39.67439, -101.33656

Cause

CauseEQUIPMENT FAILURE
SubcausePUMP OR PUMP-RELATED EQUIPMENT

Casualties

Fatalities0
Injuries0

Costs

Property Damage$3,000
Emergency Response$200
Other Costs$576

Location Map

Incident Narrative

MCDONALD PUMP STATION: PIPELINE CONTROL NOTIFIED OPERATIONS TECHNICIAN THAT A PASSERBY NOTICED VAPOR COMING FROM THE MCDONALD PUMP STATION. PIPELINE CONTROL WAS MONITORING THE LOCATION VIA CAMERA AND VERIFIED VAPOR COMING FROM THE FACILITY. THE TECHNICIAN ARRIVED SHORTLY AFTER BEING NOTIFIED AND DETERMINED NGL WAS LEAKING FROM A PUMP SEAL. IMMEDIATE CAUSE OF RELEASE WAS DETERMINED TO BE LOOSE BOLTS HOLDING SEAL GLAND IN PLACE. THE SEAL WAS REPLACED FOLLOWED BY A CHECK OF SEAL BOLTS AT OTHER ADJACENT PUMPS, WHICH WERE PROPERLY TIGHTENED AND INSTALLED. COMMUNICATION WAS MADE TO REMAINING OPERATIONS PERSONNEL RESPONSIBLE FOR PUMP STATION OPERATIONS TO CHECK SEAL GLAND RETENTION BOLTS FOR PROPER INSTALLATION AND TO IDENTIFY ANY OTHER POTENTIAL SIMILAR ISSUES.