"KINDER MORGAN LIQUID TERMINALS, LLC"

hazardous_liquid Incident — — January 18, 2018

Incident Information

Incident DateJanuary 18, 2018
Operator"KINDER MORGAN LIQUID TERMINALS, LLC"
CommodityREFINED AND/OR PETROLEUM PRODUCT (NON-HVL) WHICH IS A LIQUID
Pipeline Typehazardous_liquid

Location

State
Coordinates29.73320, -95.20490

Cause

CauseNATURAL FORCE DAMAGE
SubcauseOTHER NATURAL FORCE DAMAGE

Casualties

Fatalities0
Injuries0

Costs

Property Damage$1,000
Emergency Response$0
Other Costs$0

Location Map

Incident Narrative

"AT 11:50 ON 1-18-18 A LEAK WAS IDENTIFIED AT THE PASADENA GP MANIFOLD ON THE 20"" CROSS CHANNEL LINE. THE 4"" DRAIN VALVE HAD RUPTURED DUE TO RESIDUAL WATER FREEZING DURING AN UNNATURAL FREEZING TEMPERATURE EVENT. REPLACEMENT VALVE WAS INSTALLED. CORRECTIVE ACTION: ALL LOW POINT DRAIN VALVES IN THE FACILITY WERE CHECK TO MAKE SURE FREEZING TEMPERATURES DID NOT DAMAGE THE VALVES. PLAN TO PREVENT REOCCURRENCE: A PREVENTATIVE MAINTENANCE TASK HAS BEEN IMPLEMENTED TO INSPECT ALL LOW POINT DRAIN VALVES ON AN ANNUAL BASIS AND PRIOR TO ANY WEATHER EVENT THAT INDICATES FREEZING TEMPERATURES."

About This Pipeline Incident

Pipeline incident data is reported to the Pipeline and Hazardous Materials Safety Administration (PHMSA). All significant incidents involving fatalities, injuries, or property damage over $50,000 must be reported.