EXPLORER PIPELINE CO

hazardous_liquid Incident —

Incident Information

Report Date
OperatorEXPLORER PIPELINE CO
Commodity—
Pipeline Typehazardous_liquid

Location

State
Coordinates30.84378, -95.49514

Cause

CauseEQUIPMENT FAILURE
Subcause—

Casualties

Fatalities0
Injuries0

Costs

Property Damage
Lost Commodity
Public/Private Damage
Emergency Response
Environmental Remediation
Other Costs

Location Map

Incident Narrative

ON SEPTEMBER 27, 2016 AT 09:27 EXPLORER PERSONNEL IDENTIFIED A CHECK VALVE EAR ON UNIT 2 WAS LEAKING IN AN ENCLOSED UNDERGROUND VAULT AT THE HUNTSVILLE, TEXAS PUMP STATION. AT THE TIME OF THE EVENT, THE SUCTION SIDE OF THE CHECK VALVE WAS 270 PSIG AND THE DISCHARGE SIDE OF THE CHECK VALVE WAS 507.7 PSIG. EQUIPMENT WAS DISPATCHED AND REPAIRS WERE MADE TO THE CHECK VALVE ON SEPTEMBER 28, 2016. THE INVESTIGATION INDICATED A BUSHING AND SEAL WERE WORN ON THE CHECK VALVE. THE VALVE WAS ORIGINALLY INSTALLED IN 1973, BUT NO RECORDS REFLECT WHEN THE BUSHING OR SEALS WERE REPLACED. A MULTI YEAR PLAN IS IN REPLACE TO REPLACE THE BUSHINGS AND SEALS ON SIMILAR CHECK VALVES.