KINDER MORGAN LIQUID TERMINALS, LLC
hazardous_liquid Incident —
Incident Information
| Report Date | — |
| Operator | KINDER MORGAN LIQUID TERMINALS, LLC |
| Commodity | — |
| Pipeline Type | hazardous_liquid |
Location
| State | |
| Coordinates | 40.59064, -74.21945 |
Cause
| Cause | EQUIPMENT FAILURE |
| Subcause | — |
Casualties
| Fatalities | 0 |
| Injuries | 0 |
Costs
| Property Damage | — |
| Lost Commodity | — |
| Public/Private Damage | — |
| Emergency Response | — |
| Environmental Remediation | — |
| Other Costs | — |
Location Map
Incident Narrative
APPROXIMATELY 50 GAL. OF GASOLINE LEAKED FROM 3"" GATE VALVE DUE TO GASKET FAILURE. THE INITIAL INSPECTION INDICATES THE VALVE BONNET WAS FRACTURED ALLOWING WATER INTO A NORMALLY DRY PORTION OF THE VALVE. THE WATER FROZE AROUND THE EXISTING GASKET CAUSING AN EXPANSION AND CREATED A VOID FOR PRODUCT RELEASE.
About This Pipeline Incident
Pipeline incident data is reported to the Pipeline and Hazardous Materials Safety Administration (PHMSA). All significant incidents involving fatalities, injuries, or property damage over $50,000 must be reported.