ENTERPRISE PRODUCTS OPERATING LLC

hazardous_liquid Incident — — June 6, 2018

Incident Information

Incident DateJune 6, 2018
OperatorENTERPRISE PRODUCTS OPERATING LLC
CommodityHVL OR OTHER FLAMMABLE OR TOXIC FLUID WHICH IS A GAS AT AMBI
Pipeline Typehazardous_liquid

Location

State
Coordinates32.48630, -101.65670

Cause

CauseEQUIPMENT FAILURE
SubcausePUMP OR PUMP-RELATED EQUIPMENT

Casualties

Fatalities0
Injuries0

Costs

Property Damage$9,000
Emergency Response$1,000
Other Costs$0

Location Map

Incident Narrative

A PUMP LEAK WAS DISCOVERED BY AN ENTERPRISE TECHNICIAN DURING A ROUTINE STATION CHECK ON 6/6/18 AT 16:20. THE PUMP WAS ISOLATED AND LEAK STOPPED. A 3/4-INCH DRAIN NIPPLE ON THE BOTTOM OF THE PUMP LEAKED PRODUCT FROM A CRACK ON THE DRAIN. THE DRAIN NIPPLE AND RELATED PIPING WERE REPLACED. SUPPORT GUSSETS WERE ADDED TO THE REPLACED TUBING TO PREVENT ANY FUTURE STRESS RELATED ISSUES.

About This Pipeline Incident

Pipeline incident data is reported to the Pipeline and Hazardous Materials Safety Administration (PHMSA). All significant incidents involving fatalities, injuries, or property damage over $50,000 must be reported.

Back to All Incidents More Incidents in