SUNVIT PIPELINE LLC

hazardous_liquid Incident — — January 13, 2017

Incident Information

Incident DateJanuary 13, 2017
OperatorSUNVIT PIPELINE LLC
CommodityCRUDE OIL
Pipeline Typehazardous_liquid

Location

State
Coordinates31.94610, -101.91646

Cause

CauseEQUIPMENT FAILURE
SubcauseNON-THREADED CONNECTION FAILURE

Casualties

Fatalities0
Injuries0

Costs

Property Damage$4,500
Emergency Response$5,000
Other Costs$0

Location Map

Incident Narrative

DURING A ROUTINE FACILITY INSPECTION ON 1/13/2017 LOCAL OPERATIONS PERSONNEL DISCOVERED A RELEASE AT THE MIXER ON TANK 7112 DUE TO A MIXER SEAL FAILURE. THE MIXER WAS ISOLATED FROM THE TANK VIA THE INTERNAL SEAL DESIGN OF THE UNIT. CONTAMINATED SOIL WAS RECOVERED FOR ONSITE REMEDIATION. THE MIXER MANUFACTURER SHIMMED THE SHAFT, REPLACED THE INOARD BEARING ASSEMBLY AND THE FAILED SEAL UNDER WARRANTY. A FAILURE ANALYSIS WAS PERFORMED BY THE MANUFACTURER AND DETERMINED THAT INBOARD BEARING ASSEMBLY WEAR CAUSED VIBRATION OF THE UNIT WHICH IN TURN LED TO THE SEAL FAILURE. ADDITIONAL MIXER UNITS WERE ALSO INSPECTED FOR SIMILAR CONDITIONS AND SERVICED AND REPAIRED UNDER WARRANTY, A MODIFIED BEARING ALIGNMENT UNIT WITH AN INCREASED NUMBER OF SET SCREWS HAS BEEN INSTALLED TO PREVENT FUTURE FAILURES OF SAME OR SIMILAR NATURE.