ENTERPRISE PRODUCTS OPERATING LLC

hazardous_liquid Incident — — June 17, 2018

Incident Information

Incident DateJune 17, 2018
OperatorENTERPRISE PRODUCTS OPERATING LLC
CommodityCRUDE OIL
Pipeline Typehazardous_liquid

Location

State
Coordinates31.74570, -100.26780

Cause

CauseEQUIPMENT FAILURE
SubcausePUMP OR PUMP-RELATED EQUIPMENT

Casualties

Fatalities0
Injuries0

Costs

Property Damage$185,000
Emergency Response$450
Other Costs$0

Location Map

Incident Narrative

"AT 02:16 ON 6/17/18 ENTERPRISE PIPELINE CONTROLLER RECEIVED A SEAL FAIL ALARM ON PUMP #2 AT TENNYSON STATION, IMMEDIATELY FOLLOWED BY A FIRE ALARM, RESULTING IN THE PUMP STATION BEING SHUT DOWN AND BYPASSED. ENTERPRISE PIPELINE CONTROLLER NOTIFIED ENTERPRISE PIPELINE TECHNICIAN, AND THEN VERIFIED VIA STATION CAMERA THAT THERE WAS AN ACTUAL FIRE AT THE PUMP. PIPELINE TECHNICIAN EXTINGUISHED THE FIRE. SUBSEQUENT INSPECTION OF THE DAMAGED PUMP SEAL INDICATED THAT THE PUMP SEAL COLLAR SET SCREWS WERE UNABLE TO HOLD THE PUMP SEAL IN POSITION DUE TO INSUFFICIENT TORQUE. SIMILAR PUMP SEALS ON THIS PIPELINE ARE BEING CHECKED TO ENSURE PROPER SET SCREW TORQUE IS IN PLACE TO PREVENT RECURRENCE. NRC #1215521 48 HOUR NRC UPDATE #1215651"

About This Pipeline Incident

Pipeline incident data is reported to the Pipeline and Hazardous Materials Safety Administration (PHMSA). All significant incidents involving fatalities, injuries, or property damage over $50,000 must be reported.