WEST TEXAS GULF PIPELINE CO

hazardous_liquid Incident — — March 14, 2017

Incident Information

Incident DateMarch 14, 2017
OperatorWEST TEXAS GULF PIPELINE CO
CommodityCRUDE OIL
Pipeline Typehazardous_liquid

Location

State
Coordinates31.77745, -96.39645

Cause

CauseINCORRECT OPERATION
SubcauseTANK, VESSEL, OR SUMP/SEPARATOR ALLOWED OR CAUSED TO OVERFILL OR OVERFLOW

Casualties

Fatalities0
Injuries0

Costs

Property Damage$500
Emergency Response$2,000
Other Costs$0

Location Map

Incident Narrative

ON 3/14/2017 OPERATIONS PERSONNEL WERE CLEANING A STRAINER UPSTREAM OF THE BOOSTER PUMP ON THE OUTBOUND SYSTEM. DURING DRAIN UP PERSONNEL OBSERVED THE SUMP OVERFLOWING AND STOPPED WORK. THE DRAIN SYSTEM WAS IMMEDIATELY ISOLATED AND THE AFFECTED SOIL WAS REMEDIATED ONSITE. INVESTIGATION REVEALED THAT THE SUMP PUMP DESIGN WAS NOT ADEQUATE FOR THE VOLUME BEING DIRECTED TO THE SUMP FOR THIS WORK DUE TO THE LARGER DIAMETER LINE BEING UTILIZED FOR THE DRAIN UP OF THE STRAINER. THE QUALIFICATIONS OF THE PERSONNEL PERFORMING THE WORK WERE SUSPENDED AND RETRAINING WAS COMPLETED PRIOR TO REQUALIFICATION. TO PREVENT FUTURE RECURRENCE SUBSEQUENT STRAINER CLEANING ACTIVITIES AT THIS LOCATION WILL NECESSITATE WORK PLANNING TO DRAIN THE SUMP PRIOR TO WORK COMMENCING AND MONITORING OF SUMP LEVELS.