ONEOK NGL PIPELINE, LLC

hazardous_liquid Incident —

Incident Information

Report Date
OperatorONEOK NGL PIPELINE, LLC
Commodity—
Pipeline Typehazardous_liquid

Location

State
Coordinates29.84123, -94.89244

Cause

CauseEQUIPMENT FAILURE
Subcause—

Casualties

Fatalities0
Injuries0

Costs

Property Damage
Lost Commodity
Public/Private Damage
Emergency Response
Environmental Remediation
Other Costs

Location Map

Incident Narrative

AT APPROXIMATELY 22:20 ON 5/13/2017, ONEOK TULSA CONTROL RECEIVED A PRIORITY 1 STATION LOCK OUT ALARM DUE TO GAS DETECT AT ONEOK'S ENTERPRISE EAST DELIVERY. ONEOK PERSONNEL WERE IMMEDIATELY DISPATCHED TO THE LOCATION. UPON ARRIVAL ONEOK PERSONNEL BEGAN ISOLATING THE LEAK ON THE ONEOK 246A METER AND BLOWING DOWN THE METER THROUGH THE ENTERPRISE EAST FLARE SYSTEM. ONCE PRODUCT HAD BEEN REMOVED FROM THE METER, IT WAS DETERMINED 3/4"" PIPE NIPPLE, ON THE THERMAL RELIEF LINE, FOR THE INLET OF THE METER, HAD DEVELOPED A CRACK AND FAILED, CAUSING THE RELEASE. ONEOK'S INVESTIGATION DETERMINED A 3/4"" CHECK VALVE ON THE THERMAL PIPING, HAD FAILED IN THE OPEN POSITION, ALLOWING, HIGH RATES OF PRODUCT TO FLOW THROUGH THE 3/4"" PIPING. ONEOK REPLACED THE 3/4"" PIPE NIPPLE ALONG WITH THE CHECK VALVE ON THE THERMAL PIPING. ONEOK IS IT THE PROCESS OF REPLACING CHECK VALVES LOCATED IN SIMILAR OPERATIONS, TO PREVENT FUTURE FAILURES.