"MAGELLAN PIPELINE COMPANY, LP"

hazardous_liquid Incident — — November 14, 2018

Incident Information

Incident DateNovember 14, 2018
Operator"MAGELLAN PIPELINE COMPANY, LP"
CommodityHVL OR OTHER FLAMMABLE OR TOXIC FLUID WHICH IS A GAS AT AMBI
Pipeline Typehazardous_liquid

Location

State
Coordinates37.79278, -96.04936

Cause

CauseEQUIPMENT FAILURE
SubcausePUMP OR PUMP-RELATED EQUIPMENT

Casualties

Fatalities0
Injuries0

Costs

Property Damage$0
Emergency Response$0
Other Costs$0

Location Map

Incident Narrative

OPERATIONS CONTROL RECEIVED A SEAL FAIL ALARM FOR THE PUMP AT EUREKA STATION WHICH PROMPTED IMPLEMENTATION OF PIPELINE SHUTDOWN PROCEDURES. THE STATION WAS ISOLATED AND LOCAL PERSONNEL WERE CONTACTED TO INVESTIGATE. FIELD PERSONNEL CONFIRMED PROPANE WAS BEING RELEASED FROM THE PUMP SEALS. THE RELEASE WAS CAUSED BY POSSIBLE DEBRIS IN THE SEAL FACE. THE PUMP WAS EVACUATED OF PROPANE. THE PUMP WAS FLUSHED AND REFILLED WITH GASOLINE AND RESTARTED. NO INDICATION OF A SEAL LEAK WAS OBSERVED WHILE THE PUMP SAT IDLE IN GASOLINE OR DURING PUMP OPERATION IN GASOLINE. THE PUMP SEALS WERE MONITORED DURING THE NEXT PROPANE BATCH WITH NO SIGNS OF A SEAL LEAK. FUTURE PREVENTATIVE ACTIONS INCLUDE INSPECTING THE PUMP PER THE WEEKLY ENGINE PUMPING UNIT INSPECTION AND ANNUAL PUMPING UNIT SEAL FAILURE SYSTEM INSPECTION PROCEDURES.