DCP MIDSTREAM

hazardous_liquid Incident —

Incident Information

Report Date
OperatorDCP MIDSTREAM
Commodity—
Pipeline Typehazardous_liquid

Location

State
Coordinates28.55871, -98.16352

Cause

CauseEQUIPMENT FAILURE
Subcause—

Casualties

Fatalities0
Injuries0

Costs

Property Damage
Lost Commodity
Public/Private Damage
Emergency Response
Environmental Remediation
Other Costs

Location Map

Incident Narrative

A SMALL FROST BALL FOUND ON SCREWED FITTING AROUND PUMP 2 SUCTION BYPASS VALVE. CRACK WAS FOUND IN THE THREADS OF THE NIPPLE. THREADS WERE CUT OFF AND NIPPLE RETHREADED AND BYPASS REPLUMBED. LOST 5 GALLONS OF PRODUCT AND FLARED 123 BARRELS TO MAKE REPAIRS. TO PREVENT RECURRENCE, PUMP 2 WAS REPLACED WITH A NEWLY OVERHAULED PUMP TO REDUCE VIBRATION AND NOW VIBRATION IS MINIMAL.