IMTT-BAYONNE

hazardous_liquid Incident — — February 3, 2019

Incident Information

Incident DateFebruary 3, 2019
OperatorIMTT-BAYONNE
CommodityREFINED AND/OR PETROLEUM PRODUCT (NON-HVL) WHICH IS A LIQUID
Pipeline Typehazardous_liquid

Location

State
Coordinates40.65490, -74.11678

Cause

CauseNATURAL FORCE DAMAGE
SubcauseTEMPERATURE

Casualties

Fatalities0
Injuries0

Costs

Property Damage$4,078
Emergency Response$3,648
Other Costs$0

Location Map

Incident Narrative

"AT 1430, MIKE FROM THE HYDROCREW CALLED OVER THE RADIO ABOUT A 16"" VALVE LEAKING BY TANK 6009. RYAN O'CONNER WENT TO INVESTIGATE AND FOUND THAT THE 901 LINE TO THE FLYING A SUCTION WAS LEAKING 2 OIL. APPROXIMATELY 30 GALLONS OF 2 OIL WAS ESTIMATED ON THE GROUND AND PIPING IN THE AREA. THE IMTT TRAFFIC DEPARTMENT MADE ALL NOTIFICATIONS. THE BAYONNE FIRE DEPARTMENT ARRIVED ON SCENE AND WAS SATISFIED WITH ISOLATION AND RESPONSE BY IMTT. THE MAINTENANCE DEPARTMENT ISOLATED THE VALVE. THEY OBSERVED A BLOCK OF ICE APPROXIMATELY 2' LONG IN THE LINE. THE MAINTENANCE CREW APPLIED STEAM TO MELT THE ICE AND THEN INSTALLED A SLIP ON THE FLANGE TO ISOLATE THE LINE. THIRD-PARTY CONTRACTOR EQ WAS ALREADY ON-SITE AND MOVED TO CLEAN THE AREA AND DISPOSE OF THE DIRT ON THE DAY OF THE INCIDENT. ON 2/2/19, THE TEMPERATURE WAS 14

About This Pipeline Incident

Pipeline incident data is reported to the Pipeline and Hazardous Materials Safety Administration (PHMSA). All significant incidents involving fatalities, injuries, or property damage over $50,000 must be reported.

Back to All Incidents More Incidents in