EXXONMOBIL PRODUCTION COMPANY, A DIVISION OF EXXON MOBIL CORPORATION
hazardous_liquid Incident — — September 24, 2017
Incident Information
| Incident Date | September 24, 2017 |
| Operator | EXXONMOBIL PRODUCTION COMPANY, A DIVISION OF EXXON MOBIL CORPORATION |
| Commodity | CO2 (CARBON DIOXIDE) |
| Pipeline Type | hazardous_liquid |
Location
| State | |
| Coordinates | 41.87991, -110.04500 |
Cause
| Cause | EQUIPMENT FAILURE |
| Subcause | MALFUNCTION OF CONTROL/RELIEF EQUIPMENT |
Casualties
| Fatalities | 0 |
| Injuries | 0 |
Costs
| Property Damage | $8,824 |
| Emergency Response | $0 |
| Other Costs | $0 |
Location Map
Incident Narrative
PART H - NARRATIVE DESCRIPTION OF ACCIDENT (SUPPLEMENT TO FORM PHSMA 7000-1) THE DISCHARGE ROV'S (2643A/B/C/D) ON THE CO2 SALES COMPRESSORS A, B, C AND D TRIPPED CLOSED DUE TO PT2682 MALFUNCTION, BLOCKING COMPRESSORS OUTLET RESULTING IN SUDDEN PRESSURE INCREASE. THE CONTROL ROOM CALLED I&E TO INVESTIGATE FAILED PT2682 AND CLOSURE OF DISCHARGE ROV'S. THREE I&E TECHS RESPONDED TO CO2 SALES FOLLOWED BY THE I&E TECH FOREMAN. I&E TECH FOREMAN NOTICED SIGNIFICANT MOVEMENT IN THE DISCHARGE PIPING, DIRECTED THE TEAM TO EVACUATE THE AREA TO THE PDC AND CALLED CONTROL ROOM FOR AN E-STOP. CONTROL ROOM INITIATED CONTROLLED SHUTDOWN OF COMPRESSORS A THROUGH D WHICH WAS COMPLETED. DURING THE EVENT, COMPRESSOR DISCHARGE PIPING AND RECYCLE LINES SHOOK DAMAGING A SUPPORT BEAM ON ""A"" COMPRESSOR DISCHARGE LINE AND BROKE A 3/4 INCH DRAIN VALVE OFF COMPRESSOR ""A"" RECYCLE LINE CAUSING A LOW CO2 ALARM ON FIXED MONITORS. PERSONAL MONITORS NEVER ALARMED. ENHANCEMENTS MADE TO THE CONTROL LOGIC OF PT2682 TO ELIMINATE THE CLOSURE OF VALVES WHEN THE PRESSURE TRANSMITTER FAILS. * PART G, NO. 6 (ADDITIONAL INFORMATION) - PIPE MOVEMENT FROM THE INCREASE PRESSURE IN THE SYSTEM WAS IDENTIFIED; WOULDN'T NECESSARILY CALL THIS VIBRATION FROM UNSUPPORTED PIPE. - THE PIPING WAS SUPPORTED, DUE TO THE INCREASED PRESSURE THE PIPE MOVED.
About This Pipeline Incident
Pipeline incident data is reported to the Pipeline and Hazardous Materials Safety Administration (PHMSA). All significant incidents involving fatalities, injuries, or property damage over $50,000 must be reported.