KINDER MORGAN LIQUID TERMINALS, LLC

hazardous_liquid Incident —

Incident Information

Report Date
OperatorKINDER MORGAN LIQUID TERMINALS, LLC
Commodity—
Pipeline Typehazardous_liquid

Location

State
Coordinates29.72536, -95.20334

Cause

CauseMATERIAL FAILURE OF PIPE OR WELD
Subcause—

Casualties

Fatalities0
Injuries0

Costs

Property Damage
Lost Commodity
Public/Private Damage
Emergency Response
Environmental Remediation
Other Costs

Location Map

Incident Narrative

IN LATE SEPTEMBER A SMALL AMOUNT OF ULSD WAS OBSERVED AROUND THE TCR AREA INSIDE PASADENA TERMINAL. THE AREA WAS HYDRO EXCAVATED TO FIND THE POTENTIAL SOURCE. ON 10-2-17 THE TCR TRANSFER PUMP SUCTION PIPING WAS FOUND TO BE LEAKING PRODUCT FROM A WELD AND THE PUMP WAS SHUTDOWN. THE EQUIPMENT WAS STRIPPED OF PRODUCT AND TAKEN OUT OF SERVICE FOR REPAIRS. THE SECTION OF PIPE WAS TAKEN OFF SITE FOR TESTING. A PRESSURE TEST WAS PERFORMED (75PSI) ON THE SECTION OF PIPE OFF SITE AT WHICH TIME IT WAS CONFIRMED THAT THE WELD WAS THE SOURCE OF THE LEAK. THE PIPE WAS REPAIRED AND THE SYSTEM WAS BROUGHT BACK INTO SERVICE. THIS PIPE WAS INSTALLED PRIOR TO THE PASADENA TERMINAL BECOMING JURISDICTIONAL, AND SINCE THAT TIME PROCEDURES HAVE BEEN DEVELOPED AND REGULATORY REQUIREMENTS HAVE BEEN PUT IN PLACE TO CHECK WELDS PRIOR TO PIPE BEING PUT INTO SERVICE. THEREFORE, NO ADDITIONAL CORRECTIVE ACTIONS ARE NECESSARY.

About This Pipeline Incident

Pipeline incident data is reported to the Pipeline and Hazardous Materials Safety Administration (PHMSA). All significant incidents involving fatalities, injuries, or property damage over $50,000 must be reported.

Back to All Incidents More Incidents in