EXXONMOBIL OIL CORPORATION-TERMINALS

hazardous_liquid Incident — — October 25, 2017

Incident Information

Incident DateOctober 25, 2017
OperatorEXXONMOBIL OIL CORPORATION-TERMINALS
CommodityREFINED AND/OR PETROLEUM PRODUCT (NON-HVL) WHICH IS A LIQUID
Pipeline Typehazardous_liquid

Location

State
Coordinates41.64924, -88.04449

Cause

CauseCORROSION FAILURE
SubcauseINTERNAL CORROSION

Casualties

Fatalities0
Injuries0

Costs

Property Damage$5,000
Emergency Response$0
Other Costs$43,000

Location Map

Incident Narrative

TANK 906 AT LOCKPORT TERMINAL WAS TAKEN OUT OF SERVICE FOR API 653 INSPECTION. DURING THE INSPECTION, A THROUGH-WALL CORROSION PIT WAS DISCOVERED. AN APPROXIMATE 12'X 12' SQUARE HOLE WAS CUT IN THE TANK BOTTOM, AND SAMPLES WERE TAKEN FROM THE SOIL/WATER BETWEEN THE TANK BOTTOM AND UNDERLYING CLAY LINER. BASED UPON SAMPLING RESULTS, THE ESTIMATED RELEASE VOLUME IS APPROXIMATELY 25 GALLONS. REMNANTS OF ABRASIVE MATERIAL, OR OTHER CONTAMINANTS, FOUND UNDER THE COATING AFFECTED ITS ADHESION, WHICH COULD HAVE HASTENED THE DELAMINATION AND PREMATURE FAILURE. 06/04/2018 - UPDATED COST ESTIMATES, UPDATED VOLUME BASED ON SOIL SAMPLING RESULTS. 5/3/19 - UPDATED PART G, #7 BY SELECTING WATER DROP OUT, UPDATED #8 BY SELECTING METALLURGICAL ANALYSIS, AND UPDATED THE NARRATIVE WITH FAILURE MECHANISM INFORMATION.

About This Pipeline Incident

Pipeline incident data is reported to the Pipeline and Hazardous Materials Safety Administration (PHMSA). All significant incidents involving fatalities, injuries, or property damage over $50,000 must be reported.

Back to All Incidents More Incidents in