EQUISTAR CHEMICALS, L.P.

hazardous_liquid Incident — — November 19, 2017

Incident Information

Incident DateNovember 19, 2017
OperatorEQUISTAR CHEMICALS, L.P.
CommodityHVL OR OTHER FLAMMABLE OR TOXIC FLUID WHICH IS A GAS AT AMBI
Pipeline Typehazardous_liquid

Location

State
Coordinates28.46661, -96.93276

Cause

CauseEQUIPMENT FAILURE
SubcauseDEFECTIVE OR LOOSE TUBING OR FITTING

Casualties

Fatalities0
Injuries0

Costs

Property Damage$200
Emergency Response$2,400
Other Costs$0

Location Map

Incident Narrative

EQUISTAR PIPELINE CONTROL CENTER RECEIVED LEL ALARM AT THE TIVOLI PUMP STATION ON THE CROSS COUNTRY SYSTEM 31 VIDAURI TO PS2 (TIVOLI). THE PUMP STATION EMERGENCY SHUT-DOWN (ESD) ACTIVATED PER DESIGN, THE PUMP STATION VALVES ALIGNED TO BY-PASS THE STATION AND THE PRESSURE WITHIN THE PUMP STATION WAS SENT TO THE FLARE. ON-CALL TECHNICIANS WERE DISPATCHED TO INVESTIGATE THE ALARM AND ESD. AT 1:05AM ON 11/20/2017, THE TECHNICIANS DISCOVERED A 3/8IN STAINLESS STEEL TUBING TO A PRESSURE TRANSMITTER HAD FAILED ON THE PUMP DISCHARGE. THE TUBING WAS REPLACED AND SUBSEQUENTLY THE PUMP STATION WAS BROUGHT BACK ONLINE. THE INVESTIGATION REVEALED THE TUBING FAILURE WAS DUE TO HIGH CYCLE, LOW STRESS MECHANICAL FATIGUE SUGGESTING HIGH-FREQUENCY VIBRATION AS THE LIKELY CAUSE. THE TUBING WAS CONNECTED TO A PRESSURE TRANSMITTER WHICH WAS MOUNTED IN A MANNER THAT AMPLIFIED VIBRATIONS TRANSFERRED FROM THE PUMP DISCHARGE PIPING. TO PREVENT RECURRENCE THE PRESSURE TRANSMITTER WILL BE REMOUNTED TO ADDRESS HIGH FREQUENCY VIBRATION AND THE INVESTIGATION FINDINGS AND CORRECTIVE ACTION WILL BE COMMUNICATED TO EMPLOYEES.

About This Pipeline Incident

Pipeline incident data is reported to the Pipeline and Hazardous Materials Safety Administration (PHMSA). All significant incidents involving fatalities, injuries, or property damage over $50,000 must be reported.

Back to All Incidents More Incidents in