"DELEK LOGISTICS OPERATING, LLC."

hazardous_liquid Incident — — May 6, 2019

Incident Information

Incident DateMay 6, 2019
Operator"DELEK LOGISTICS OPERATING, LLC."
CommodityCRUDE OIL
Pipeline Typehazardous_liquid

Location

State
Coordinates32.35415, -93.67843

Cause

CauseINCORRECT OPERATION
Subcause"TANK, VESSEL, OR SUMP/SEPARATOR ALLOWED OR CAUSED TO OVERFILL OR OVERFLOW"

Casualties

Fatalities0
Injuries0

Costs

Property Damage$0
Emergency Response$5,000
Other Costs$0

Location Map

Incident Narrative

THE FINNEY PIPELINE STARTED A SCHEDULED MOVEMENT. AFTER SEVERAL MINUTES THE F1 METER BEGAN TO SHOW NO FLOW. THE CONTROLLER SHUT DOWN THE SHIPMENT AND DISARMED THE STATION BECAUSE OF THE NO FLOW SITUATION. THE CONTROLLER CONTACTED THE MAINTENANCE MANAGER TO TROUBLESHOOT THE METER. AN OPERATOR WHO WAS TRAVELING IN THE AREA WAS SENT TO PERFORM MAINTENANCE ON THE METER. THE CONTROLLER RESTARTED THE LINE RUNNING THROUGH THE F3 METER INSTEAD OF F1. THE MAINTENANCE MANAGER INSTRUCTED THE OPERATOR OVER THE PHONE WHILE HE WORKED ON THE EQUIPMENT. THE MAINTENANCE MANAGER DIRECTED THE OPERATOR TO OPEN AN INCORRECT VALVE DURING THE MAINTENANCE. THE OPEN VALVE DIRECTED OIL TO THE SUMP RESULTING IN AN OVERFLOW RELEASING 3 BARRELS TO THE GROUND. THE OPERATOR IMMEDIATELY CLOSED THE VALVE. PERSONNEL WERE DISPATCHED TO CLEAN THE SPILLED CRUDE.

About This Pipeline Incident

Pipeline incident data is reported to the Pipeline and Hazardous Materials Safety Administration (PHMSA). All significant incidents involving fatalities, injuries, or property damage over $50,000 must be reported.