DURING THE FACILITY CHECK, LOCAL OPERATIONS DISCOVERED DIESEL FUEL IN THE CONTAINMENT AREA AROUND TANK 6045. UPON INVESTIGATING THE RELEASE ORIGIN, A CRACKED FLANGE ON THE WATER DRAW VALVE WAS DISCOVERED. COLD TEMPERATURES CAUSED ACCUMULATED WATER IN THE FLANGE TO CRACK. THE WATER DRAW VALVE WAS CLOSED TO STOP THE RELEASE AND THE IMPACTED FLANGE WAS REPLACED. THE WATER DRAW VALVES ON THE REST OF THE TANKS AT THE FACILITY WERE CLOSED. THE EXISTING BULL PLUGS WERE REMOVED AND REPLACED WITH SOLID BULL PLUGS. NO ICE WAS FOUND AT THE OTHER TANKS. VISUAL INSPECTION OF THE FLANGES SHOWED NO EVIDENCE OF CRACKING. APPROXIMATELY 75 CUBIC YARDS OF SOIL WAS REMEDIATED SUPPLEMENTAL/FINAL FILED: UPDATE TO PART E 5F 10/03/2024 - UPDATED BY PHMSA PER OPERATOR APPROVAL.