MAGELLAN PIPELINE COMPANY, LP

hazardous_liquid Incident —

Incident Information

Report Date
OperatorMAGELLAN PIPELINE COMPANY, LP
Commodity—
Pipeline Typehazardous_liquid

Location

State
Coordinates37.80231, -96.87143

Cause

CauseEQUIPMENT FAILURE
Subcause—

Casualties

Fatalities0
Injuries0

Costs

Property Damage
Lost Commodity
Public/Private Damage
Emergency Response
Environmental Remediation
Other Costs

Location Map

Incident Narrative

AT 13:16 ON 1/21/18 A HAZARDOUS GAS ALARM WAS RECEIVED BY OPERATIONS CONTROL. PLC PROGRAMMING ASSOCIATED WITH THE HAZARDOUS GAS ALARM AUTOMATICALLY SHUT DOWN PUMPS P1010 AND P1030 LOCATED IN THE PUMP BUILDING AT EL DORADO EAST. SUCTION AND DISCHARGE VALVES WERE AUTOMATICALLY CLOSED WHEN THE UNIT SHUT DOWN. ONCE THE PUMP ROOM WAS DEEMED SAFE FOR ENTRY, LOCAL PERSONNEL CLOSED THE ISOLATION VALVES FOR P1010. THE PUMP WAS DRAINED AND FREE PRODUCT ON THE PUMP BASED WAS CLEANED WITH ABSORBENT PADS AND VAC TRUCK. LOCAL PERSONNEL INVESTIGATED AND FOUND P1010 WAS LEAKING FROM THE BALANCE TUBE ON THE PUMP CASE. VIBRATION RESONANCE ON THE BALANCE LINE CAUSED A CRACK IN THE WELD. SULZER WAS CALLED OUT TO PERFORM REPAIRS. SULZER COMPLETED A NEW WELD AND INSTALLED A BRACKET TO ABSORB/DAMPEN THE VIBRATION.