ON 2/9/18 A LAND OWNER NEAR THE ONEOK GOAT JUNCTION CALLED ONEOK PERSONNEL TO INFORM THEM SHE COULD SEE A SMALL VAPOR CLOUD INSIDE THE ONEOK FACILITY. UPON ARRIVAL, THE LOCAL AREA REPRESENTATIVE DISCOVERED PRODUCT VAPORS COMING FROM THE VALVE BODY OF A DRAIN VALVE INSTALLED ON THE SCRAPER TRAP BARREL. THE SCRAPER TRAP BARREL WAS ISOLATED AND DE-PRESSURED. THE 2"" BALON DRAIN VALVE WAS REMOVED FROM THE SCRAPER TRAP AND A BLIND FLANGE INSTALLED. THE SCRAPER TRAP WAS THEN RETURNED TO NORMAL OPERATIONS. ONEOK'S INVESTIGATION DETERMINED THE O-RING IN THE VALVE BODY HAD FAILED CAUSING THE RELEASE. THE O-RING HAS BEEN SENT TO A LAB TO DETERMINE THE CAUSE OF FAILURE. 3/16/2018 - UPDATED TIME OF ACCIDENT (A-4), VERIFIED LAT./LONG. PER REQUEST OF OCC. 7/05/2018 - UPDATED INVESTIGATION OF O-RING DETERMINED O-RING TO BE COMPATIBLE WITH PRODUCT IN PIPELINE. CAUSE OF FAILURE OF O-RING WAS INCONCLUSIVE.