DCP MIDSTREAM
hazardous_liquid Incident —
Incident Information
| Report Date | — |
| Operator | DCP MIDSTREAM |
| Commodity | — |
| Pipeline Type | hazardous_liquid |
Location
| State | |
| Coordinates | 29.59965, -95.19417 |
Cause
| Cause | INCORRECT OPERATION |
| Subcause | — |
Casualties
| Fatalities | 0 |
| Injuries | 0 |
Costs
| Property Damage | — |
| Lost Commodity | — |
| Public/Private Damage | — |
| Emergency Response | — |
| Environmental Remediation | — |
| Other Costs | — |
Location Map
Incident Narrative
THE 4-21-18 RELEASE THAT OCCURRED AT ELLINGTON PUMP STATION (PS) WAS DUE TO AN ACCIDENTAL ACTIVATION, BY A CONTRACTOR, OF THE MONT BELVIEU STATION'S (MBS) ESD WHICH IS LOCATED DOWNSTREAM OF THE ELLINGTON PS. CONSEQUENTLY, THIS LED TO A PRESSURE INCREASE AT THE ELLINGTON PS WHICH CAUSED THE THERMAL RELIEF VALVES TO LIFT AND DISCHARGE PRODUCT TO THE STATION VENT STACK. AS A RESULT, A REVIEW OF ESD SWITCHES WAS CONDUCTED AND ADDITIONAL SAFEGUARDS SUCH AS SWITCH COVERS, ARE BEING EVALUATED AND WILL BE INSTALLED ACCORDINGLY.