MAGELLAN PIPELINE COMPANY, LP

hazardous_liquid Incident —

Incident Information

Report Date
OperatorMAGELLAN PIPELINE COMPANY, LP
Commodity—
Pipeline Typehazardous_liquid

Location

State
Coordinates40.20050, -104.60806

Cause

CauseINCORRECT OPERATION
Subcause—

Casualties

Fatalities0
Injuries0

Costs

Property Damage
Lost Commodity
Public/Private Damage
Emergency Response
Environmental Remediation
Other Costs

Location Map

Incident Narrative

DURING MORNING FACILITY INSPECTION, OPERATOR OBSERVED PRODUCT ON THE CONCRETE CONTAINMENT FLOOR ORIGINATING FROM THE BOTTOM OF THE FLANGE IN THE TRANSFER MANIFOLD AREA. THE LINE WAS NOT RUNNING AT THE TIME. CLEAN UP ACTIVITIES WERE COMMENCED BY USING DIAPERS AND SOLVENTS. FURTHER INVESTIGATION IDENTIFIED A THERMAL PSV ON THE LINE SEGMENT WAS ISOLATED. DUE TO THE PSV BEING ISOLATED, IT IS BELIEVED THE LINE BECAME PRESSURIZED DUE TO THERMAL PRESSURE AND LIKELY EXCEEDED MOP, RESULTING IN THE RELEASE AT THE FLANGE. THE FLANGE GASKET AND BOLTS WERE REPLACED AND THE TRANSFER MANIFOLD VISUALLY INSPECTED. A SAFETY MEETING WAS CONDUCTED AND DUTIES OF DAILY FACILITY AND EQUIPMENT INSPECTIONS WERE RE-ENFORCED ALONG WITH A REVIEW OF THE PSV INSPECTION PROCEDURE