ENTERPRISE PRODUCTS OPERATING LLC
hazardous_liquid Incident —
Incident Information
| Report Date | — |
| Operator | ENTERPRISE PRODUCTS OPERATING LLC |
| Commodity | — |
| Pipeline Type | hazardous_liquid |
Location
| State | |
| Coordinates | 31.74570, -100.26780 |
Cause
| Cause | EQUIPMENT FAILURE |
| Subcause | — |
Casualties
| Fatalities | 0 |
| Injuries | 0 |
Costs
| Property Damage | — |
| Lost Commodity | — |
| Public/Private Damage | — |
| Emergency Response | — |
| Environmental Remediation | — |
| Other Costs | — |
Location Map
Incident Narrative
AT 02:16 ON 6/17/18 ENTERPRISE PIPELINE CONTROLLER RECEIVED A SEAL FAIL ALARM ON PUMP #2 AT TENNYSON STATION, IMMEDIATELY FOLLOWED BY A FIRE ALARM, RESULTING IN THE PUMP STATION BEING SHUT DOWN AND BYPASSED. ENTERPRISE PIPELINE CONTROLLER NOTIFIED ENTERPRISE PIPELINE TECHNICIAN, AND THEN VERIFIED VIA STATION CAMERA THAT THERE WAS AN ACTUAL FIRE AT THE PUMP. PIPELINE TECHNICIAN EXTINGUISHED THE FIRE. SUBSEQUENT INSPECTION OF THE DAMAGED PUMP SEAL INDICATED THAT THE PUMP SEAL COLLAR SET SCREWS WERE UNABLE TO HOLD THE PUMP SEAL IN POSITION DUE TO INSUFFICIENT TORQUE. SIMILAR PUMP SEALS ON THIS PIPELINE ARE BEING CHECKED TO ENSURE PROPER SET SCREW TORQUE IS IN PLACE TO PREVENT RECURRENCE. NRC #1215521 48 HOUR NRC UPDATE #1215651