ENTERPRISE PRODUCTS OPERATING LLC
hazardous_liquid Incident —
Incident Information
| Report Date | — |
| Operator | ENTERPRISE PRODUCTS OPERATING LLC |
| Commodity | — |
| Pipeline Type | hazardous_liquid |
Location
| State | |
| Coordinates | 30.01387, -94.05370 |
Cause
| Cause | EQUIPMENT FAILURE |
| Subcause | — |
Casualties
| Fatalities | 0 |
| Injuries | 0 |
Costs
| Property Damage | — |
| Lost Commodity | — |
| Public/Private Damage | — |
| Emergency Response | — |
| Environmental Remediation | — |
| Other Costs | — |
Location Map
Incident Narrative
ON JUNE 17, 2018 AT 19:44, THE CONTROL ROOM RECEIVED A HAZARDOUS GAS ALARM ON THE BEAUMONT ATEX UNIT 14C. PERSONNEL WERE DISPATCHED TO THE SITE AT 20:25 TO FIND THE 3/8 INCH STAINLESS STEEL TUBING LINE FOR THE SUCTION PRESSURE TRANSMITTER WAS CRACKED APPROXIMATELY 2 INCHES BELOW THE TRANSMITTER. THE LINE WAS ISOLATED AND THE LEAK STOPPED. THERE WERE 5 BARRELS OF ETHANE RELEASED WITH NO FIRE, EVACUATION, OR INJURY THAT WERE CAUSED BY THIS INCIDENT. THE TUBING WAS ORIGINALLY INSTALLED WITHOUT A SUPPORT; THEREFORE, THE TUBING WAS REPLACED, SUPPORTS WERE ADDED, AND HAS BEEN PUT BACK INTO SERVICE. ADDITIONALLY, WE ADDED SUPPORTS TO THE OTHER UNITS A AND B AS A PRECAUTIONARY MEASURE.