DCP MIDSTREAM

hazardous_liquid Incident — — November 19, 2019

Incident Information

Incident DateNovember 19, 2019
OperatorDCP MIDSTREAM
CommodityHVL OR OTHER FLAMMABLE OR TOXIC FLUID WHICH IS A GAS AT AMBI
Pipeline Typehazardous_liquid

Location

State
Coordinates29.08966, -96.62664

Cause

CauseINCORRECT OPERATION
SubcauseOTHER INCORRECT OPERATION

Casualties

Fatalities0
Injuries0

Costs

Property Damage$250
Emergency Response$0
Other Costs$0

Location Map

Incident Narrative

"THE WILBREEZE PUMP STATION UNIT# 2 WAS SHUTDOWN AND ISOLATED TO CONDUCT MAINTENANCE ON THE PUMP SEAL. WHILE DCP EMPLOYEES WERE REMOVING THE BEARING COUPLING, A FLASHFIRE OCCURRED AT 13:32 THAT WAS DETECTED BY THE FIRE EYES DETECTION SYSTEM AND TRIGGERED THE ESD WHICH CAUSED THE WILBREEZE PUMP STATION SHUTDOWN. THE ROOT CAUSE WAS NOT HAVING AN ADEQUATE PROCEDURE WHILE HEATING A MECHANICAL COMPONENT WITH A TORCH TO REMOVE OR INSTALL BEARING OR HUBS. THE PROCEDURE HAS BEEN REVISED TO INCLUDE GUIDANCE THAT ALL TUBING MUST BE CONNECTED AND LEFT INTACT WHILE REMOVING OR INSTALLING THE BEARING COUPLING. THE TRAINING WILL BE CONDUCTED FOR FIELD EMPLOYEES BASED ON THE NEW REVISED PROCEDURE."