"KINDER MORGAN LIQUID TERMINALS, LLC"

hazardous_liquid Incident — — December 2, 2019

Incident Information

Incident DateDecember 2, 2019
Operator"KINDER MORGAN LIQUID TERMINALS, LLC"
CommodityREFINED AND/OR PETROLEUM PRODUCT (NON-HVL) WHICH IS A LIQUID
Pipeline Typehazardous_liquid

Location

State
Coordinates29.72363, -95.20170

Cause

CauseMATERIAL FAILURE OF PIPE OR WELD
Subcause"DESIGN-, CONSTRUCTION-, INSTALLATION-, OR FABRICATION-RELATED"

Casualties

Fatalities0
Injuries0

Costs

Property Damage$56,000
Emergency Response$0
Other Costs$0

Location Map

Incident Narrative

"ON 12/2/19 A KM OPERATOR FOUND A 2OZ LEAK INSIDE PIT 4. A PINHOLE LEAK WAS IDENTIFIED IN THE BOTTOM HEADER OF PIT 4, THE SECTION OF PIPE WAS ISOLATED, THE PRODUCT WAS CLEANED AND THE WELD REPAIRED. THE SADDLE WELD INSTALLED BY GATX IN 1977 WAS NOT DESIGNED TO ENDURE THE MECHANICAL STRESS CAUSE BY 40 YEARS OF WEAR. PLAN TO PREVENT REOCCURANCE: WELD WAS GRINDED OUT AND NEW WELD INSTALLED WITH THICKER METAL PER CURRENT KINDER MORGAN STANDARDS. OTHER WELDS IN PIT 4 TO BE INSPECTED TO IDENTIFY CURRENT CONDITION AND REPAIR OR REPLACE AS NECESSARY."