ONEOK NGL PIPELINE, LLC

hazardous_liquid Incident —

Incident Information

Report Date
OperatorONEOK NGL PIPELINE, LLC
Commodity—
Pipeline Typehazardous_liquid

Location

State
Coordinates35.54874, -99.29455

Cause

CauseEQUIPMENT FAILURE
Subcause—

Casualties

Fatalities0
Injuries0

Costs

Property Damage
Lost Commodity
Public/Private Damage
Emergency Response
Environmental Remediation
Other Costs

Location Map

Incident Narrative

AT APPROXIMATELY 11:17 ON 8/10/2018 THE ONEOK PANTHER CREEK PLANT OPERATOR NOTIFIED THE LOCAL PIPELINE OPERATOR OF A LEAK ON THE LIQUIDS PIPELINE METER SKID. THE SOURCE OF THE LEAK WAS IDENTIFIED TO BE THE YZ SAMPLE PUMP ON THE METER SKID. THE SAMPLE PUMP WAS REPLACED AND THE METER SKID WAS RETURNED TO SERVICE. UPON INVESTIGATION, IT WAS DETERMINED THAT A POSSIBLE CAUSE WAS VIBRATION FROM THE CUSTOMER'S PLANT PD PUMPS. THE CUSTOMER EVALUATED THE TWO PUMPS AND REPLACED THE DISCHARGE PULSATION STABILIZER BLADDERS ON BOTH OF THEM. IN ADDITION, THE CUSTOMER HAS SETUP A PREVENTATIVE MAINTENANCE PROGRAM TO EVALUATE THE PULSATION STABILIZERS QUARTERLY. A VIBRATION SWITCH HAS ALSO BEEN INSTALLED ON THE ONEOK NGL METER SKID AS AN ALARM TO NOTIFY THE ONEOK NGL PIPELINE CONTROL CENTER.