DCP MIDSTREAM

hazardous_liquid Incident —

Incident Information

Report Date
OperatorDCP MIDSTREAM
Commodity—
Pipeline Typehazardous_liquid

Location

State
Coordinates32.41270, -93.11680

Cause

CauseEQUIPMENT FAILURE
Subcause—

Casualties

Fatalities0
Injuries0

Costs

Property Damage
Lost Commodity
Public/Private Damage
Emergency Response
Environmental Remediation
Other Costs

Location Map

Incident Narrative

PRESSURE TRANSMITTER WAS DAMAGED AND GAS DETECTORS ACTIVATED WHEN TUBING FITTING FAILED AND LEAKING NGL IGNITED. THIS LED TO ALMOST IMMEDIATE AUTOMATED ESD OF THE STATION. OPERATIONS PERSONNEL WERE NEARBY, AND ON SITE SHORTLY AFTER RECEIVING NOTIFICATION FROM CONTROL CENTER. WITHIN 30 MINUTES IT WAS DETERMINED TO BE SAFE TO CLOSE THE TAP VALVE ON THE TUBING LINE, ALLOWING THE FIRE TO BURN ITSELF OUT. ALL DAMAGED EQUIPMENT WAS REPLACED PRIOR TO RESTART OF THE METER STATION.

About This Pipeline Incident

Pipeline incident data is reported to the Pipeline and Hazardous Materials Safety Administration (PHMSA). All significant incidents involving fatalities, injuries, or property damage over $50,000 must be reported.