Cause

CauseEQUIPMENT FAILURE
Subcause—

Casualties

Fatalities0
Injuries0

Costs

Property Damage
Lost Commodity
Public/Private Damage
Emergency Response
Environmental Remediation
Other Costs

Location Map

Incident Narrative

DURING LOADING ACTIVITIES TO THE SHIP DOCK, OPERATIONS PERSONNEL DISCOVERED A PUMP SEAL LEAK ON TANK PUMP 392. LOADING ACTIVITIES WERE IMMEDIATELY SHUT DOWN. THE PUMP WAS ISOLATED AND CLEAN UP ACTIVITIES COMMENCED. IMPACTED SOIL WAS EXCAVATED, CONTAINERIZED AND PROPERLY DISPOSED. THE RELEASE ORIGINATED FROM A PUMP SEAL FAILURE DUE TO IMPROPER INSTALLATION. THE PUMP SEAL WAS REPLACED. LEFT-HANDED THREADS WERE USED AS A PRECAUTION TO PREVENT THE ROTATION OF THE PUMP FROM LOOSENING THE SEAL. SEAL MANUFACTURER'S RECOMMENDED MAINTENANCE PROCEDURES WILL BE REVIEWED AND FOLLOWED. SUPPLEMENTAL/FINAL (05/10/2019): UPDATED PART G6-6 AND PART H SUPPLEMENTAL/FINAL (05/21/2019): REVIEW PART G PER REQUEST BY TRRC