"KINDER MORGAN LIQUID TERMINALS, LLC"

hazardous_liquid Incident — — April 8, 2020

Incident Information

Incident DateApril 8, 2020
Operator"KINDER MORGAN LIQUID TERMINALS, LLC"
CommodityREFINED AND/OR PETROLEUM PRODUCT (NON-HVL) WHICH IS A LIQUID
Pipeline Typehazardous_liquid

Location

State
Coordinates29.73166, -95.19928

Cause

CauseEQUIPMENT FAILURE
SubcauseTHREADED CONNECTION/COUPLING FAILURE

Casualties

Fatalities0
Injuries0

Costs

Property Damage$50
Emergency Response$0
Other Costs$0

Location Map

Incident Narrative

"ON APRIL 8, 2020, AN OPERATOR DISCOVERED PRODUCT COMING FROM A THREADED PIPE CONNECTION ON THE PRV PIPING NEAR THE TCR PUMP. THE PRODUCT WAS CLEANED UP AND THE CRACKED PIPE NIPPLE WAS REPLACED. DURING THE INVESTIGATION, IT WAS DISCOVERED THAT THE PIPE NIPPLE CRACKED DUE TO STRESS ON THE PIPE CAUSED BY IMPROPER SUPPORT. PLAN TO PREVENT RECURRENCE: ADDITIONAL SUPPORT HAS BEEN ADDED AND PIPING MODIFICATIONS HAVE BEEN MADE TO REDUCE THE VIBRATION OF THE PIPING NEAR THE PUMP."