"ENLINK PERMIAN, LLC"

hazardous_liquid Incident — — May 6, 2020

Incident Information

Incident DateMay 6, 2020
Operator"ENLINK PERMIAN, LLC"
CommodityCRUDE OIL
Pipeline Typehazardous_liquid

Location

State
Coordinates29.12495, -97.38711

Cause

CauseINCORRECT OPERATION
Subcause"TANK, VESSEL, OR SUMP/SEPARATOR ALLOWED OR CAUSED TO OVERFILL OR OVERFLOW"

Casualties

Fatalities0
Injuries0

Costs

Property Damage$0
Emergency Response$10,000
Other Costs$0

Location Map

Incident Narrative

"ON MAY 6, 2020 AT APPROXIMATELY 10:00 A.M., OPERATIONS PERSONNEL DISCOVERED A SPILL OF CRUDE OIL FROM THE METER SKID AT BARTHOLOMEW PUMP STATION. THE SPILL WAS THE RESULT OF A LOW DRAIN 1"" BALL VALVE BEING OPENED ALLOWING OIL TO FREE FLOW INTO A SITE SUMP WHICH ULTIMATELY OVERFLOWED INTO A SKID PAN. ONCE AT CAPACITY, THE SKID PAN THEN ALLOWED THE FREE-FLOWING OIL TO SPILL ONTO THE LANDSCAPE IN THE FACILITY. DUE TO A RECENT RAINFALL EVENT, THE OIL THEN FLOWED OFFSITE THROUGH A CULVERT INTO A ROADSIDE DITCH BEFORE FINALLY BEING CONTAINED IN A SECTION OF A DRAINAGE DITCH ON AN ADJACENT LANDOWNER'S PROPERTY. AT A LATER TIME ENLINK PERFORMED A ROOT CAUSE ANALYSIS AND REVIEWED ALL PERTINENT DATA AND CONCLUDED, SINCE NO ONE HAD DONE ANY MAINTENANCE OR REPAIRS ON THIS SKID, OPERATOR ERROR WAS NOT A FACTOR. THE FACILITY PERIMETER FENCING SHOWS NO SIGNS OF BREAKING AND ENTERING, RULING OUT SABOTAGE/VANDALISM. THE TEAM DETERMINED THE ROOT CAUSE WAS MORE LIKELY THAN NOT CAUSED BY A FAILED HIGH-LEVEL SUMP SWITCH, ALONG WITH THE VALVE GOING TO ATMOSPHERE NOT BEING PROPERLY LOCKED OR CAR SEALED, ALLOWED PRODUCT TO OVERFILL THE SUMP, IN TURN ALLOWING PRODUCT TO ESCAPE INTO A NEARBY NON-FLOWING DRAINAGE DITCH."

About This Pipeline Incident

Pipeline incident data is reported to the Pipeline and Hazardous Materials Safety Administration (PHMSA). All significant incidents involving fatalities, injuries, or property damage over $50,000 must be reported.

Back to All Incidents More Incidents in