MAGELLAN TERMINALS HOLDINGS, LP

hazardous_liquid Incident —

Incident Information

Report Date
OperatorMAGELLAN TERMINALS HOLDINGS, LP
Commodity—
Pipeline Typehazardous_liquid

Location

State
Coordinates29.74523, -95.20083

Cause

CauseEQUIPMENT FAILURE
Subcause—

Casualties

Fatalities0
Injuries0

Costs

Property Damage
Lost Commodity
Public/Private Damage
Emergency Response
Environmental Remediation
Other Costs

Location Map

Incident Narrative

DURING TRANSFER ACTIVITIES, OPERATIONS PERSONNEL OBSERVED PRODUCT BEING RELEASED FROM THE OUTBOARD SIDE OF THE PUMP AT THE MANIFOLD. FRICTION FROM THE SEAL FAILURE CAUSED THE PRODUCT TO IGNITE AND RESULTED IN A SMALL FIRE. OPERATOR IMMEDIATELY SHUTDOWN THE PUMP AND USED A FIRE EXTINGUISHER TO EXTINGUISH THE FIRE. ONCE THE FIRE WAS PUT OUT, THE PUMP WAS ISOLATED. THE RELEASE ORIGINATED FROM A PUMP SEAL FAILURE LIKELY CAUSED BY MISALIGNMENT DUE TO PIPE STRAIN. THE PUMP WAS REMOVED AND SENT TO A SHOP FOR INSPECTION. PIPING MODIFICATIONS WILL BE MADE PRIOR TO INSTALLING AND PLACING THIS PUMP BACK IN SERVICE.

About This Pipeline Incident

Pipeline incident data is reported to the Pipeline and Hazardous Materials Safety Administration (PHMSA). All significant incidents involving fatalities, injuries, or property damage over $50,000 must be reported.

Back to All Incidents More Incidents in