MAGELLAN TERMINALS HOLDINGS, LP
hazardous_liquid Incident —
Incident Information
| Report Date | — |
| Operator | MAGELLAN TERMINALS HOLDINGS, LP |
| Commodity | — |
| Pipeline Type | hazardous_liquid |
Location
| State | |
| Coordinates | 35.95866, -96.71950 |
Cause
| Cause | EQUIPMENT FAILURE |
| Subcause | — |
Casualties
| Fatalities | 0 |
| Injuries | 0 |
Costs
| Property Damage | — |
| Lost Commodity | — |
| Public/Private Damage | — |
| Emergency Response | — |
| Environmental Remediation | — |
| Other Costs | — |
Location Map
Incident Narrative
DURING TANK FARM INSPECTION, OPERATIONS PERSONNEL DISCOVERED CRUDE OIL AROUND THE CHIME OF A NEWLY CONSTRUCTED TANK. THE TANK WAS IN THE PROCESS OF BEING FILLED. TRANSFER OPERATIONS WERE SHUT DOWN AND CLEAN UP ACTIVITIES WERE INITIATED. THE TANK HAS BEEN EMPTIED AND CLEANED. PRELIMINARY INSPECTION REVEALED A HOLE IN A FILLET WELD ON THE INTERIOR FLOOR PLATES. COUPONS WERE CUT FROM THE TANK FLOOR AND THE COUPON CONTAINING THE FAILURE WAS SENT FOR ANALYSIS. RESULTS OF THE ANALYSIS INDICATE THE LEAK WAS DUE TO A LOCALIZED INADEQUATE PENETRATION WELD DEFECT IN THE SUBMERGED ARC FILLET WELD. 48-HOUR NRC UPDATE: #1233459, 12/19/2018 11:10 SUPPLEMENTAL/FINAL (04/29/2019): UPDATED PART G6 AND PART H SUPPLEMENTAL/FINAL (05/09/2019): UPDATED PART C3 AND G5 SUPPLEMENTAL/FINAL 07/08/2019): UPDATED PART C3 AND G6 SUPPLEMENTAL/FINAL 06/16/2020): UPDATED PART A7 (DATE CORRECTION)
About This Pipeline Incident
Pipeline incident data is reported to the Pipeline and Hazardous Materials Safety Administration (PHMSA). All significant incidents involving fatalities, injuries, or property damage over $50,000 must be reported.