DCP MIDSTREAM

hazardous_liquid Incident —

Incident Information

Report Date
OperatorDCP MIDSTREAM
Commodity—
Pipeline Typehazardous_liquid

Location

State
Coordinates31.22687, -101.62194

Cause

CauseEQUIPMENT FAILURE
Subcause—

Casualties

Fatalities0
Injuries0

Costs

Property Damage
Lost Commodity
Public/Private Damage
Emergency Response
Environmental Remediation
Other Costs

Location Map

Incident Narrative

A LEAK WAS DISCOVERED ON THE INLINE STRAINER TO PUMP 300 AT BENEDUM PUMP STATION ON 12/27/18 BY DCP EMPLOYEE ON SITE. THE PUMP WAS IMMEDIATELY SHUT DOWN AND ISOLATED. DETERMINED CAUSE OF THE FAILURE IN 3/4"" THREADED NIPPLE LOCATED ON THE BOTTOM OF THE STRAINER DRAIN WAS DUE TO EXCESSIVE VIBRATION. CORRECTIVE ACTION: VIBRATIONS ANALYSIS WAS PERFORMED ON STATION PIPING ON 1/8/19. THE DETERMINATION WAS MADE THAT THE 3/4"" STRAINER DRAINS BLOW DOWNS LOCATED ON STATION PUMP STRAINERS BE REMOVED. THE BLOW DOWNS AND PIPING WERE NOT NECESSARY AND NOT NEEDED. BLOWDOWNS AND PIPING WERE REMOVED.