SFPP, LP

hazardous_liquid Incident —

Incident Information

Report Date
OperatorSFPP, LP
Commodity—
Pipeline Typehazardous_liquid

Location

State
Coordinates33.84543, -118.23295

Cause

CauseEQUIPMENT FAILURE
Subcause—

Casualties

Fatalities0
Injuries0

Costs

Property Damage
Lost Commodity
Public/Private Damage
Emergency Response
Environmental Remediation
Other Costs

Location Map

Incident Narrative

WHILE CONDUCTING SHIFT INSPECTION, OPERATOR DISCOVERED AN APPROXIMATELY 5.5 INCH THICK LAYER OF DIESEL ON TOP OF APPROXIMATELY 24"" OF RAINWATER IN THE VAULT OF TANK 5. THE TANK WAS DRAINED DRY, THE ROOF WAS LANDED ON LEGS AND THE TANK BEGAN A CLEANING PROCESS SO NATURE AND LOCATION OF THE LEAK COULD BE DETERMINED. AS OF 3/7/2019, THE WATSON-5 TANK WAS DISCOVERED TO HAVE 2 CRACKS BUT THE CAUSE OF WHAT CAUSED THE CRACKS ARE STILL UNDER INVESTIGATION. UPDATE 6/24/2019 FOR SUPPLEMENTAL/FINAL SUBMISSION: SUBSEQUENT INVESTIGATION FOUND A 3/4"" CRACK UNDER THE COVER PLATE AT A SQUARED/90 DEGREE ANGLE CORNER WELD NEAR WHERE THE BEARING PLATE MEETS THE BOTTOM PLATE. CRACKED MATERIAL WAS REMOVED, RE-WELDED AND A 12"" PATCH PLATE WAS INSTALLED OVER THE REPAIRED AREA. 09/30/2024 - UPDATED BY PHMSA PER OPERATOR APPROVAL.