ENTERPRISE CRUDE PIPELINE LLC

hazardous_liquid Incident —

Incident Information

Report Date
OperatorENTERPRISE CRUDE PIPELINE LLC
Commodity—
Pipeline Typehazardous_liquid

Location

State
Coordinates31.06891, -98.73287

Cause

CauseEQUIPMENT FAILURE
Subcause—

Casualties

Fatalities0
Injuries0

Costs

Property Damage
Lost Commodity
Public/Private Damage
Emergency Response
Environmental Remediation
Other Costs

Location Map

Incident Narrative

ON MARCH 4, 2019 AT 8:08 AM AN ENTERPRISE PIPELINE TECHNICIAN DISCOVERED A CRUDE OIL LEAK AT THE CHEROKEE PUMP STATION. PIPELINE CONTROL WAS IMMEDIATELY NOTIFIED AND THE PUMP STATION WAS ISOLATED. THE INCIDENT WAS DETERMINED TO BE NRC REPORTABLE AT 9:35 AM. IMPROPER INSTALLATION AND COMMISSIONING OF PRESSURE RELIEF EQUIPMENT RESULTED IN AN OVERFLOW OF THE SURGE TANK. SECONDARY CONTAINMENT SYSTEM FAILED, RESULTING IN RELEASE TO ADJOINING PROPERTY. SCADA TANK LEVEL ALARMS DID NOT PROVIDE ASSISTANCE IN IDENTIFYING THE ACCIDENT BECAUSE OF INCORRECT INSTALLATION OF TANK LEVEL GAUGES DURING CONSTRUCTION. ENVIRONMENTAL REMEDIATION IS IN PROGRESS. NRC INITIAL #1239181 AND 48-HOUR UPDATE #1239359 TRRC ACCIDENT #1949

About This Pipeline Incident

Pipeline incident data is reported to the Pipeline and Hazardous Materials Safety Administration (PHMSA). All significant incidents involving fatalities, injuries, or property damage over $50,000 must be reported.

Back to All Incidents More Incidents in