NUSTAR LOGISTICS, L.P.
hazardous_liquid Incident — — May 8, 2019
Incident Information
| Incident Date | May 8, 2019 |
| Operator | NUSTAR LOGISTICS, L.P. |
| Commodity | CRUDE OIL |
| Pipeline Type | hazardous_liquid |
Location
| State | |
| Coordinates | 33.91311, -98.43587 |
Cause
| Cause | EQUIPMENT FAILURE |
| Subcause | DEFECTIVE OR LOOSE TUBING OR FITTING |
Casualties
| Fatalities | 0 |
| Injuries | 0 |
Costs
| Property Damage | $120 |
| Emergency Response | $1,800 |
| Other Costs | $2,962 |
Location Map
Incident Narrative
DURING A WEATHER-RELATED POWER OUTAGE, A NUSTAR EMPLOYEE DISCOVERED A CRUDE OIL LEAK AT NUSTAR'S WICHITA FALLS PUMP STATION WHILE PREPARING THE STATION FOR RESTART. A 3/4-INCH STEEL COOLING TUBING SEPARATED FROM THE STATION'S UNIT NO. 2 OUTBOARD BEARING. A PRESSURE SPIKE WITHIN THE UNIT NO. 2 SUCTION PIPING, CAUSED BY THE FAILURE OF A PUMP STATION CHECK VALVE, CONTRIBUTED TO THE FAILURE OF THE TUBING FITTING. THE TUBING FITTING HAS BEEN REMOVED AND SENT TO A LABORATORY FOR ANALYSIS. THE TUBING FITTING AND CHECK VALVE HAVE BEEN REPLACED. UPDATE - THE FAILURE WAS DUE TO INCOMPLETE INSTALLATION OF THE TUBING IN THE FITTING. FITTING FERRULES WERE INADEQUATELY SEATED ON THE TUBING.