KINDER MORGAN LIQUID TERMINALS, LLC

hazardous_liquid Incident —

Incident Information

Report Date
OperatorKINDER MORGAN LIQUID TERMINALS, LLC
Commodity—
Pipeline Typehazardous_liquid

Location

State
Coordinates29.72855, -95.20215

Cause

CauseEQUIPMENT FAILURE
Subcause—

Casualties

Fatalities0
Injuries0

Costs

Property Damage
Lost Commodity
Public/Private Damage
Emergency Response
Environmental Remediation
Other Costs

Location Map

Incident Narrative

ON 7/30/2019, A KM OPERATOR FOUND A LEAK ON THE TCR CAN STRIPPING PUMP. APPROXIMATELY 12 GALLONS OF GASOLINE LEAKED THROUGH THE THREATED CONNECTION ON THE INTERNAL FLUSH LINE OF THE PUMP. REMEDIATION BEGAN IMMEDIATELY, THE ASSET WAS STRIPPED AND ISOLATED. THE PUMP WAS PULLED FROM THE CAN AND SENT OUT FOR REPAIRS. THE CAUSE OF THE LEAK WAS DETERMINED TO BE CORROSION ON THE THREADS OF THE FITTING CAUSED BY COLLECTION OF WATER IN THE PUMP HEAD. PLAN TO PREVENT REOCCURRENCE - TO PREVENT THE ACCUMULATION OF WATER FROM OCCURRING IN THE PUMP HEAD, KM NOW HAS A MOUSEHOLE, FOR WATER DRAINING, BE ADDED TO THE PUMP HEAD DURING SERVICING AND INSPECTION OF THE PUMPS.