DCP MIDSTREAM

hazardous_liquid Incident —

Incident Information

Report Date
OperatorDCP MIDSTREAM
Commodity—
Pipeline Typehazardous_liquid

Location

State
Coordinates31.78229, -102.24995

Cause

CauseINCORRECT OPERATION
Subcause—

Casualties

Fatalities0
Injuries0

Costs

Property Damage
Lost Commodity
Public/Private Damage
Emergency Response
Environmental Remediation
Other Costs

Location Map

Incident Narrative

CONTRACTOR WAS SEPARATING A 6 INCH, 600 SERIES FLANGE INSIDE THE DCP SAND HILLS ROBERTS RANCH METER STATION DURING A SCHEDULED MAINTENANCE JOB. METER STATION HAD BEEN ISOLATED AND PREPARED FOR MAINTENANCE PRIOR TO THE SCHEDULED MAINTENANCE EVENT. CONTRACTOR WAS USING AN ELECTRIC IMPACT WRENCH TO UNBOLT A 6 INCH, 600 SERIES FLANGE. THE CONTRACTOR WAS DOWN TO THE LAST BOLT AND NUT, WHEN THE FLANGE SEPARATED APART RELEASING NGL VAPOR WHICH FOUND AN IGNITION SOURCE (ELECTRIC IMPACT) CAUSING SMALL FLASH FIRE. THE FIRE WATCH EXTINGUISHED IMMEDIATELY. NO DAMAGE OR INJURIES. NOTE: PART A #8, #9 & #10 MINIMUM AMOUNT OF 0.1 WAS ENTERED BECAUSE THE FORM WILL NOT ALLOW ZERO ENTRY. NO NGL LIQUIDS WERE RELEASED/ONLY VAPORS WERE RELEASED. CORRECTIVE ACTION: REVIEW OF GROUNDING & BONDING POLICY O&M MANUAL, SECTION F-08 PREVENTION OF ACCIDENTAL IGNITION WITH SAHI WEST OPERATIONS COMPLETED 8/27/19. ALSO COMMUNICATED TO SAHI WEST OPERATIONS EMPLOYEES ON 8/27/19 THAT ELECTRIC IMPACT WRENCHES WILL NOT BE USED. PROHIBITED USE OF SPARK PRODUCING ELECTRIC IMPACT WRENCHES.

About This Pipeline Incident

Pipeline incident data is reported to the Pipeline and Hazardous Materials Safety Administration (PHMSA). All significant incidents involving fatalities, injuries, or property damage over $50,000 must be reported.

Back to All Incidents More Incidents in