ENTERPRISE PRODUCTS OPERATING LLC

hazardous_liquid Incident —

Incident Information

Report Date
OperatorENTERPRISE PRODUCTS OPERATING LLC
Commodity—
Pipeline Typehazardous_liquid

Location

State
Coordinates31.74313, -98.37388

Cause

CauseEQUIPMENT FAILURE
Subcause—

Casualties

Fatalities0
Injuries0

Costs

Property Damage
Lost Commodity
Public/Private Damage
Emergency Response
Environmental Remediation
Other Costs

Location Map

Incident Narrative

ON 8/26/19 AT 23:47 ENTERPRISE PIPELINE CONTROL RECEIVED A HAZGAS ALARM FOLLOWED BY A PUMP SHUTDOWN AT SHIN OAK ENERGY EAST PUMP STATION. A PIPELINE TECHNICIAN ARRIVED ON SITE AT 01:30 ON 8/27/19 AND DISCOVERED THAT THE RELEASE CAME FROM A WELD BY THREAD SWAGE FITTING ON THE THERMAL BYPASS LINE ON THE PUMP #2 DISCHARGE VALVE. AN EQUIPMENT RELIABILITY SUBJECT MATTER EXPERT EXAMINED THE SWAGE FITTING AND DETERMINED THAT THE CAUSE OF THE RELEASE WAS A CRACK ON THE THREADED END OF THE FITTING. TO PREVENT RECURRENCE, THE STANDARD DESIGN FOR THERMAL RELIEF SYSTEMS TO BE USED AT ENTERPRISE FACILITIES WAS UPDATED TO MITIGATE VIBRATION. THE COMMODITY, HVL, AND AMOUNT RELEASED DURING THIS LEAK DID NOT CONTAMINATE THE AREA OR REQUIRE ENVIRONMENTAL REMEDIATION. TRRC INCIDENT #2050