KINDER MORGAN LIQUID TERMINALS, LLC

hazardous_liquid Incident —

Incident Information

Report Date
OperatorKINDER MORGAN LIQUID TERMINALS, LLC
Commodity—
Pipeline Typehazardous_liquid

Location

State
Coordinates38.84420, -90.08950

Cause

CauseEQUIPMENT FAILURE
Subcause—

Casualties

Fatalities0
Injuries0

Costs

Property Damage
Lost Commodity
Public/Private Damage
Emergency Response
Environmental Remediation
Other Costs

Location Map

Incident Narrative

ON 10/12/2019 AT 7:55 A.M. A CONTRACTOR REPORTED THE SMELL OF GASOLINE TO AN OPERATOR. AFTER SECURING THE AREA, THE OPERATOR IDENTIFIED THE SOURCE OF THE 36 BARREL LEAK TO BE COMING FROM THE J242 PUMP. THE PUMP WAS ISOLATED AND THE PRODUCT CLEANNED WITH A VAC-TRUCK. AFTER FURTHER INVESTIGATION IT WAS DETERMINED THAT THE PUMP BODY HAD CRACKED DO TO THERMAL STRESS. AN OVERNIGHT TEMPERATURE SWING FROM 65 DEGREES TO 34 DEGREES GENERATED A THERMAL STRESS TRANSFER FROM THE PIPE WHICH CAUSED THE PUMP BODY TO FAIL. A NEW PUMP HAS BEEN ORDERED AND WILL BE INSTALLED UPON ARRIVAL.

About This Pipeline Incident

Pipeline incident data is reported to the Pipeline and Hazardous Materials Safety Administration (PHMSA). All significant incidents involving fatalities, injuries, or property damage over $50,000 must be reported.

Back to All Incidents More Incidents in