PLANTATION PIPE LINE CO
hazardous_liquid Incident — — February 17, 2020
Incident Information
| Incident Date | February 17, 2020 |
| Operator | PLANTATION PIPE LINE CO |
| Commodity | REFINED AND/OR PETROLEUM PRODUCT (NON-HVL) WHICH IS A LIQUID |
| Pipeline Type | hazardous_liquid |
Location
| State | |
| Coordinates | 38.73266, -77.19230 |
Cause
| Cause | EQUIPMENT FAILURE |
| Subcause | MALFUNCTION OF CONTROL/RELIEF EQUIPMENT |
Casualties
| Fatalities | 0 |
| Injuries | 0 |
Costs
| Property Damage | $18 |
| Emergency Response | $26,600 |
| Other Costs | $0 |
Location Map
Incident Narrative
ON MONDAY, 2/17/2020, AT APPROXIMATELY 0930, THE FACILITY PERSONNEL IDENTIFIED A LARGE STAIN ON GRAVEL NEAR THE SUMP ASSOCIATED WITH 6DA & 6WA (OUTBOUND) PIPELINES. FURTHER INVESTIGATION REVEALED THAT A RELEASE FROM THE SUMP HAD OCCURRED. THE SUMP IS EQUIPPED WITH A HIGH-LEVEL SHUT-DOWN SWITCH THAT PROVIDES AN ALARM AND AUTOMATIC SHUT-DOWN (ASD) OF THE PUMPING EQUIPMENT. THIS SWITCH DID NOT FUNCTION AS EXPECTED ALLOWING THE SUMP TO OVERFLOW.