ENTERPRISE PRODUCTS OPERATING LLC

hazardous_liquid Incident — — January 19, 2022

Incident Information

Incident DateJanuary 19, 2022
OperatorENTERPRISE PRODUCTS OPERATING LLC
CommodityREFINED AND/OR PETROLEUM PRODUCT (NON-HVL) WHICH IS A LIQUID
Pipeline Typehazardous_liquid

Location

State
Coordinates39.02580, -85.85030

Cause

CauseEQUIPMENT FAILURE
SubcauseNON-THREADED CONNECTION FAILURE

Casualties

Fatalities0
Injuries0

Costs

Property Damage$2
Emergency Response$250
Other Costs$0

Location Map

Incident Narrative

"ON 01/19/2022, AT APPROXIMATELY 21:55 EST, AN ENTERPRISE OPERATOR AT SEYMOUR TERMINAL NOTICED A SMALL FIRE ON THE HEAT TAPE ON MOV-0741. THE FIRE WAS EXTINGUISHED WITH A HAND HELD EXTINGUISHER AND POWER TO THE HEAT TAPE WAS DISCONNECTED. INVESTIGATION THE FOLLOWING MORNING DETERMINED THAT AN ELECTRICAL SHORT ON THE HEAT TAPE IGNITED GASOLINE FROM A SMALL PACKING LEAK ORIGINATING FROM THE VALVE STEM BONNET. HEAT TAPE WAS REMOVED AND VALVE WAS INSPECTED AND REPACKED. NRC#: 1326914 ON 1/20/2022 AT 7:04 EST 48HR NRC#: 1327021 ON 1/21/2022 AT 12:31 EST"