KINDER MORGAN LIQUID TERMINALS, LLC

hazardous_liquid Incident —

Incident Information

Report Date
OperatorKINDER MORGAN LIQUID TERMINALS, LLC
Commodity—
Pipeline Typehazardous_liquid

Location

State
Coordinates29.72755, -95.19969

Cause

CauseINCORRECT OPERATION
Subcause—

Casualties

Fatalities0
Injuries0

Costs

Property Damage
Lost Commodity
Public/Private Damage
Emergency Response
Environmental Remediation
Other Costs

Location Map

Incident Narrative

ON MAY 11, 2020 AT 7:00 PM, AN OPERATOR DISCOVERED A STAIN NEAR THE COLONIAL MANIFOLD AND AN INVESTIGATION TO IDENTIFY THE SOURCE BEGAN. ON MAY 12, 2020 AT 1:30 PM, IT WAS DETERMINED THAT THE SOURCE WAS A BLOCK AND BLEED VALVE. THE BLOCK AND BLEED WAS ISOLATED AND THE PRODUCT WAS CLEANED UP. THE CAVITY DRAIN VALVE WAS INADVERTENTLY IN AN OPEN POSITION DUE TO IT BEING INSTALLED IN THE WRONG ORIENTATION. THE VALVE WAS INSTALLED IN AN INCORRECT ORIENTATION (UPSIDE DOWN) PREVENTING THE LOCKING MECHANISM FROM ENGAGING AND MAKING IT SUSCEPTIBLE TO BEING UNKNOWINGLY OPENED. KM HAS A SIGNIFICANT NUMBER OF CONTRACTORS WORKING IN THE AREA OF THE VALVE, MAKING THIS A TEMPORARILY HIGH TRAFFICKED AREA DUE TO A CURRENT PROJECT. THE LAST WORK PERFORMED ON THE VALVE WAS ROUTINE MAINTENANCE TO REPLACE AN ACTUATOR. THE ACTUATOR REPLACEMENT DOES NOT REQUIRE THE VALVE TO BE OPENED, HOWEVER, TO WORK ON THE ACTUATOR SCAFFOLDING HAD TO BE INSTALLED. KMLT HAS AN OQ COVERED TASK FOR OPENING AND CLOSING VALVES, HOWEVER, DUE TO THE ACTUATOR REPLACEMENT NOT REQUIRING THE VALVE TO BE OPENED OR CLOSED THIS TASKS WAS NOT PART OF THE WORK. THE EMPLOYEE WAS OQ QUALIFIED TO REPLACE THE ACTUATOR. IT IS LIKELY THAT THE CAVITY DRAIN VALVE WAS INADVERTENTLY BRUSHED OPENED DURING THE INSTALLATION/DISASSEMBLY OF THE SCAFFOLDING AROUND THE VALVE. PLAN FOR PREVENTION: THESE VALVES ARE BEING REPLACED WITH SPRING LOADED VALVES TO AVOID THIS TYPE OF INCIDENT FROM OCCURRING AGAIN.

About This Pipeline Incident

Pipeline incident data is reported to the Pipeline and Hazardous Materials Safety Administration (PHMSA). All significant incidents involving fatalities, injuries, or property damage over $50,000 must be reported.

Back to All Incidents More Incidents in