ONEOK NGL PIPELINE, LLC

hazardous_liquid Incident —

Incident Information

Report Date
OperatorONEOK NGL PIPELINE, LLC
Commodity—
Pipeline Typehazardous_liquid

Location

State
Coordinates31.43558, -94.76016

Cause

CauseEQUIPMENT FAILURE
Subcause—

Casualties

Fatalities0
Injuries0

Costs

Property Damage
Lost Commodity
Public/Private Damage
Emergency Response
Environmental Remediation
Other Costs

Location Map

Incident Narrative

ON MAY 13TH AT APPROXIMATELY 3:50 PM, AT THE ONEOK LUFKIN PUMP STATION, A SEAL FAIL WAS IDENTIFIED ON THE OB SEAL OF PUMP #2. THE OPERATOR ISOLATED AND FLARED DOWN THE PUMP AND MADE ALL INTERNAL NOTIFICATIONS AS REQUIRED. THE SEAL AND RELATED COMPONENTS WERE REPLACED AND THE PUMP WAS PLACED BACK IN SERVICE. THE FAILED SEAL WAS SENT TO THE MANUFACTURER FOR FAILURE ANALYSIS WHICH REVEALED THE FAILURE OF THE SEAL WAS CAUSED BY THE EXCESSIVE AMOUNT OF AXIAL THRUST, WHICH WAS DUE TO THE THRUST BEARING RETAINER ANTI-ROTATION TAB BEING WORN DOWN. THIS SPINNING OF THE THRUST BEARING'S OUTER RACE ALLOWED THE THRUST END PLATE TO WEAR RAPIDLY UNTIL THE OVERALL THRUST OF THE PUMP CAUSED THE FAILURE.

About This Pipeline Incident

Pipeline incident data is reported to the Pipeline and Hazardous Materials Safety Administration (PHMSA). All significant incidents involving fatalities, injuries, or property damage over $50,000 must be reported.