ENTERPRISE CRUDE PIPELINE LLC

hazardous_liquid Incident —

Incident Information

Report Date
OperatorENTERPRISE CRUDE PIPELINE LLC
Commodity—
Pipeline Typehazardous_liquid

Location

State
Coordinates31.52707, -103.56026

Cause

CauseEQUIPMENT FAILURE
Subcause—

Casualties

Fatalities0
Injuries0

Costs

Property Damage
Lost Commodity
Public/Private Damage
Emergency Response
Environmental Remediation
Other Costs

Location Map

Incident Narrative

ON 06/16/2020 AT 10:15 AM, AN ENTERPRISE TECHNICIAN PERFORMING STATION CHECKS DISCOVERED CRUDE OIL COMING FROM THE C94 PIPELINE BOOSTER PUMP SEAL. THE PUMP WAS NOT RUNNING AT THE TIME OF AN ACCIDENT. THE FAILED SEAL, AND ITS COMPONENTS, WERE REPLACED AND SENT FOR EXAMINATION. THE EXAMINATION CONCLUDED THE FAILURE OF THE GASKETS IS LIKELY RELATED TO USING TWO INSTEAD OF ONE GASKET. BY BEING STACKED TOGETHER, THE GASKETS WERE NOT ABLE TO ACHIEVE SUFFICIENT COMPRESSIVE LOAD TO PREVENT DEFORMATION AND FAILURE.

About This Pipeline Incident

Pipeline incident data is reported to the Pipeline and Hazardous Materials Safety Administration (PHMSA). All significant incidents involving fatalities, injuries, or property damage over $50,000 must be reported.

Back to All Incidents More Incidents in