ENTERPRISE PRODUCTS OPERATING LLC

hazardous_liquid Incident —

Incident Information

Report Date
OperatorENTERPRISE PRODUCTS OPERATING LLC
Commodity—
Pipeline Typehazardous_liquid

Location

State
Coordinates29.84652, -94.89646

Cause

CauseEQUIPMENT FAILURE
Subcause—

Casualties

Fatalities0
Injuries0

Costs

Property Damage
Lost Commodity
Public/Private Damage
Emergency Response
Environmental Remediation
Other Costs

Location Map

Incident Narrative

AT APPROXIMATELY 19:44 CT ON 08/03/2020, ENTERPRISE PIPELINE CONTROL RECEIVED A HAZARDOUS GAS DETECTOR ALARM AT THE MONT BELVIEU SOUTH TERMINAL. AN ENTERPRISE EMPLOYEE WAS DISPATCHED TO THE SITE ARRIVING AT 20:30. THE SOURCE OF THE RELEASE WAS LOCATED AND LINE WAS ISOLATED. ENTERPRISE BLEW DOWN APPROXIMATELY 1300 BARRELS TO REDUCE LINE PRESSURE TO 0 PSI, MONITORING LEL LEVELS THROUGHOUT. A GASKET ON A VALVE FAILED ALLOWING PRODUCT TO ESCAPE. THERE WAS NO INDICATION THAT THE PRESSURE EXCEEDED THE MOP OF THE SYSTEM AND THE ENTERPRISE SYSTEM WAS NOT FLOWING AT THE TIME OF THE RELEASE. THE FAILED GARLOCK GASKET WAS REPLACED WITH A FLEXITALLIC GASKET TO STOP THE LEAK FROM RECURRING. GARLOCK GASKETS WILL BE REPLACED WITH FLEXITALLIC GASKETS WITHIN THIS FACILITY TO PREVENT RECURRENCE OF A SIMILAR EVENT. NRC INITIAL CALL # 1283608, NRC 48-HR FOLLOW-UP # 1283776.

About This Pipeline Incident

Pipeline incident data is reported to the Pipeline and Hazardous Materials Safety Administration (PHMSA). All significant incidents involving fatalities, injuries, or property damage over $50,000 must be reported.

Back to All Incidents More Incidents in