PEOPLES GAS SYSTEM INC
gas_distribution Incident — CORAL SPRINGS, FL — December 6, 2019
Incident Information
| Incident Date | December 6, 2019 |
| Operator | PEOPLES GAS SYSTEM INC |
| Commodity | NATURAL GAS |
| Pipeline Type | gas_distribution |
Location
| City | CORAL SPRINGS |
| State | FL |
| County | DADE-BROWARD |
| Coordinates | 26.24595, -80.25332 |
Cause
| Cause | EXCAVATION DAMAGE |
| Subcause | EXCAVATION DAMAGE BY THIRD PARTY |
Casualties
| Fatalities | 0 |
| Injuries | 0 |
Costs
| Property Damage | $83,388 |
| Emergency Response | $8,870 |
| Other Costs | $648 |
Location Map
Incident Narrative
"CONTRACTOR, JM POWER, STRUCK A 6"" PE MAIN WHILE BORING UNDER A CANAL. JM POWER DID NOT SUBMIT AN UNDERWATER TICKET AS REQUIRED BY FS CHAPTER 556; THEREFORE, THE CANAL WAS NOT MARKED WITH BUOYS. TWO 2"" BYPASSES WERE BUILT TO CONTINUE GAS FLOW, 6 INCH PIPE WAS SQUEEZED AFTER. CREWS, VERIFIED NO PRESSURE DROPS AFTER BYPASS WAS INSTALLED. TO MAKE FINAL REPAIRS, A PIECE OF 4"" PE WAS INSERTED INTO THE DAMAGED AREA. 6"" X 4"" REDUCERS WERE INSTALLED ON EITHER SIDE OF THE INSERTED PIPE. COST INFORMATION IS DOES NOT INCLUDE RESTORATION (WHICH SHOULD BRING THE COSTS TO OVER $50K); WILL UPDATE WITH A SUPPLEMENTAL WHEN FINAL COSTS ARE RECEIVED. SUPPLEMENTAL CREATED: ADDED TOTALS OF RESTORATION AND ADDITIONAL CONTRACTOR CHARGES.. COSTS ARE FINAL."