ENTERPRISE PRODUCTS OPERATING LLC

hazardous_liquid Incident —

Incident Information

Report Date
OperatorENTERPRISE PRODUCTS OPERATING LLC
Commodity—
Pipeline Typehazardous_liquid

Location

State
Coordinates29.95470, -94.24220

Cause

CauseEQUIPMENT FAILURE
Subcause—

Casualties

Fatalities0
Injuries0

Costs

Property Damage
Lost Commodity
Public/Private Damage
Emergency Response
Environmental Remediation
Other Costs

Location Map

Incident Narrative

ON OCTOBER 8TH, 2020 AT 02:50 CDT THE CHEEK PUMP 1801 SHUT DOWN DUE TO A SEAL FAIL ALARM. THE PUMP SUCTION AND DISCHARGE VALVES WERE AUTOMATICALLY CLOSED AND PROPANE WITHIN THE PUMP CASING WAS AUTOMATICALLY VENTED. THE CONTROLLER SHUT DOWN THE PIPELINE AND ISOLATED THE STATION. A TECHNICIAN ARRIVED AT THE STATION AND CONFIRMED THE PUMP EXPERIENCED A SEAL FAIL; PRODUCT WAS NOT RELEASED FROM THE SEAL. THE PIPELINE WAS RESTARTED USING A DIFFERENT PUMP AT CHEEK STATION AT 04:10 CDT. THE PUMP WAS REMOVED AND SENT TO A SHOP WHERE DEBRIS WAS FOUND IN THE PUMP. THE DEBRIS CAUSED THE PUMP SEALS TO COME OUT OF ALIGNMENT AND TRIGGERED THE SEAL FAIL ALARM. THE PUMP WAS CLEANED AND REPAIRED THEN REINSTALLED AT CHEEK STATION ON 2/12/2021.

About This Pipeline Incident

Pipeline incident data is reported to the Pipeline and Hazardous Materials Safety Administration (PHMSA). All significant incidents involving fatalities, injuries, or property damage over $50,000 must be reported.

Back to All Incidents More Incidents in