"ONEOK NGL PIPELINE, LLC"

hazardous_liquid Incident — — August 27, 2022

Incident Information

Incident DateAugust 27, 2022
Operator"ONEOK NGL PIPELINE, LLC"
CommodityHVL OR OTHER FLAMMABLE OR TOXIC FLUID WHICH IS A GAS AT AMBI
Pipeline Typehazardous_liquid

Location

State
Coordinates29.85340, -94.89279

Cause

CauseINCORRECT OPERATION
SubcauseEQUIPMENT NOT INSTALLED PROPERLY

Casualties

Fatalities0
Injuries0

Costs

Property Damage$200
Emergency Response$800
Other Costs$0

Location Map

Incident Narrative

"ON 8/27/2022 ONEOK AND CONTRACTOR PERSONNEL WERE PERFORMING WORK CONNECTING NEW HEADER PIPING TO EXISTING HEADER PIPING AT ONEOK MONT BELVIEU PUMP STATION. THE EXISTING HEADER PIPING HAD BEEN ISOLATED AND EVACUATED OF PRODUCT IN ADDITION TO A WELDING BLANKET PLACED IN PREPARATION FOR THE NEW CONNECTION AND ASSOCIATED WELDING. DURING THE WELDING PROCEDURE THE FIRE WATCH NOTICED A SMALL, NON-PRESSURIZED FIRE ON THE FLANGE CONNECTING THE NEW AND EXISTING HEADER PIPING. THE FIRE WAS IMMEDIATELY EXTINGUISHED AND WORK HALTED. ONEOK'S ON SITE INVESTIGATION FOUND THAT DURING THE WELDING PROCEDURE THE FLANGE/SPEC BLIND CONNECTION OF THE NEW TO EXISTING HEADER PIPING WAS NOT PROPERLY TORQUED. AN ISOLATION VALVE USED TO ISOLATE FROM ACTIVE PIPING HAD A SMALL LEAK-BY INTO THE EVACUATED PIPING CAUSING A RELEASE OF LESS THAN 0.25 GALLONS OF PRODUCT AT THE IMPROPERLY TORQUED FLANGE/SPEC BLIND. DESPITE THERE BEING NO VAPORS DETECTED USING LEL MONITORS PRIOR TO WELDING AND DURING GRINDING ACTIVITIES, THE SMALL VAPOR RELEASE FROM THE FLANGE IGNITED DURING GRINDING CAUSING THE SMALL FIRE."

About This Pipeline Incident

Pipeline incident data is reported to the Pipeline and Hazardous Materials Safety Administration (PHMSA). All significant incidents involving fatalities, injuries, or property damage over $50,000 must be reported.

Back to All Incidents More Incidents in